SMA Solar Technology AG 17 Technical Data
Installation Manual SCCPXT-IA-D7-en-42 81
Output Data
Nominal AC power at +50°C 760kVA
Continuous AC power at +25°C 836kVA
Maximum AC current 1,411 A
AC
Nominal AC current 1,283 A
AC
Nominal AC voltage − 10% / +15% 342V
AC
Power frequency 50Hz/60Hz
Displacement power factor cos φ 0.9
lagging
to 0.9
leading
Maximum total harmonic distortion < 3%
Overvoltage category - AC output III
Overvoltage category - communication II
Power Consumption
Self-consumption in operation < 1,900 W
Standby consumption <100W
External supply voltage 230V / 400 V (3/N/PE), 50Hz/60Hz
Dimensions and Weight
Width x height x depth 2,562 mm x 2,272 mm x 956 mm
Weight 1,900 kg
Efficiency
Maximum efficiency, η
max
98.6%
European weighted efficiency, η
EU
98.4%
CEC weighted efficiency 98.5%
Ambient Conditions
Degree of protection: electronics / connection area
(as per IEC 60529)
IP54 / IP43
Pollution degree 2
Operating temperature range ‒25°C to +62°C
Extended temperature range*
* Only for Sunny Central with option "-40°C"
‒40°C to +62°C
Humidity 15% to 95%
Fresh air consumption 3,000 m
3
/h
Maximum operating altitude above MSL**
** For installation at altitudes over 2,000 m, the maximum DC and MPP voltage values change (see Technical Information "High-Altitude
Installation").
4,000 m