Problem Cause and corrective measure
The diagrams are empty or incom-
plete.
No energy meters or not all energy meters are connected
to the SunnyHomeManager or they are not configured.
Corrective measures:
• Connect the energy meters to the
SunnyHomeManager and configure them (see the
installation manual of the SunnyHomeManager).
SunnyPortal cannot receive any data from the
SunnyHomeManager.
Corrective measures:
• Make sure that the connection between the
SunnyHomeManager and the SunnyPortal is
established (see the installation manual of the
SunnyHomeManager).
Data on the following pages is not up
to date:
• Current Status And Forecast
• Energy balance on the
Current tab
• Load balance and control on
the Current tab
Settings in the router prevent SunnyPortal from requesting
current data from the SunnyHomeManager.
Corrective measures:
• Ensure that the following requirements are fulfilled
– All UDP ports > 1024 on the router or modem
must be open for outgoing connections. If there
is a firewall installed on the router or modem,
you might have to adjust the firewall rules.
– It must be possible for the outgoing router or
modem connections to reach all Internet
destinations (target IP, target port). If there is a
firewall installed on the router or modem, you
might have to adjust the firewall rules.
– On the router or modem with NAT (Network
Address Translation) there must not be any port
forwarding. Potential communication problems
can thus be prevented.
– There must be no packet filtering or
manipulation for SIP packets on the router or
modem.
An exclamation mark is permanently
displayed after parameters have been
changed.
SunnyPortal could not transfer the parameters to the
SunnyHomeManager.
Corrective measures:
• Make sure that the connection between the
SunnyHomeManager and the SunnyPortal is
established (see the installation manual of the
SunnyHomeManager).
15 Troubleshooting