SMA Solar Technology AG Technical Data
Technical Description SI2012_2224-TEN082311 199
Load limits for multi-function relays 1 and 2:
connection to ohmic loads
connection to strongly inductive loads
AC1: 6.0 A at 250 V~
AC15: 1.2 A
at 250 V~
AC1: 6.0 A at 250 V~
AC15: 1.2 A
at 250 V~
Interruption time
Maximal interruption time 50 ms 50 ms
Mechanical data
Width x height x depth (470 x 445 x 185) mm (470 x 445 x 185) mm
Weight approx. 18 kg approx. 18 kg
Ambient conditions
Ambient temperature from –25 °C to +60 °C from –25 °C to +60 °C
Miscellaneous
Guaranty (EU) 5 years 5 years
Accessories
External battery temperature sensor included included
Generator Manager (GenMan) optional optional
External DC fuse (BatFuse) required (not included in
delivery)
required (not included in
delivery)
External DC charge controllers (SIC40) optional optional
* The technical data for the SI 2012 are preliminary
SI 2012* SI 2224