3 Information on Off-Grid Systems and System Description SMA Solar Technology AG
14 Off-Grid-IS-en-30 Installation - Quick Reference Guide
3.2.4 Multicluster System
Figure4: Block circuit diagram
Multicluster systems consist of several three-phase clusters. The individual clusters must be connected to a Multicluster Box.
The Multicluster Box is the AC main distribution board in a multicluster system. If the device types within the cluster are
different, the master must be an SI8.0H-11.
3.3 Information on Off-Grid Systems
Required device types for multicluster systems
In multicluster systems, the Sunny Island inverters must be device type SI6.0H-11 or SI8.0H-11.
Information on batteries
Lithium-ion batteries in off-grid systems
In order to meet the requirements of off-grid systems, the Sunny Island has a high overload capacity. The prerequisite
for this overload capacity is that the battery is able to supply sufficient current. With lithium-ion batteries, this ampacity
cannot be taken for granted.
Check with the battery manufacturer whether the battery is suitable for off-grid systems with Sunny Island
inverters. Pay special attention to the ampacity.
Recommendations for battery capacity
SMA Solar Technology AG recommends the following minimum battery capacities.
Minimum battery capacity per Sunny Island inverter:
SI3.0M-11: 100 Ah
SI4.4M-11: 150 Ah
SI6.0H-11: 190 Ah
SI8.0H-11: 250 Ah
Minimum battery capacity per 1,000 Wp power of the PV system: 100 Ah
The sum of the individual battery capacities is the total minimum battery capacity and applies to a ten-hour electric
discharge (C10). The minimum battery capacity must be observed to ensure stable operation of the system.