SMA Solar Technology AG 5 Single-Cluster System
Installation - Quick Reference Guide Off-Grid-IS-en-30 33
Set the maximum generator current per line conductor for
continuous operation.
Confirm the basic configuration with Y.
Confirm Setup Slaves ? with Y.
Wait until the upper LED (inverter LED) on slave 1 is flashing and the Sunny Remote Control is displaying
To identify Slave1, press Tss on the Slv.
Press the start-stop button on slave 1.
Wait until the Sunny Remote Control displays To identify Slave2, press Tss on the Slv.
In off-grid systems without slave 2, press the button on the
Sunny Remote Control.
In off-grid systems with slave 2, wait until the inverter LED
flashes on slave 2.
Press the start-stop button on slave 2.
☑ The basic configuration is complete. If an SD memory card is
inserted into the Sunny Remote Control,
the message Do not remove MMC/SD memory card ... appears
and the SD memory card is integrated in the file system.
Commission the off-grid system (see Section7, page39).