SMA America, LLC 19 Parameter Lists
Technical description SI4548_6048-US-TB_en-13 173
233# Grid Start
No. Name Description Value Explanation Default
value
01 GdSocTm1Str SOC limit for
switching on the
grid for time 1
40%
02 GdSocTm1Stp SOC limit for
switching off the
grid for time 1
80%
03 GdSocTm2Str SOC limit for
switching on the
grid for time 2
40%
04 GdSocTm2Stp SOC limit for
switching off the
grid for time 2
80%
05 GdTm1Str Time 1 for grid
request in hours,
minutes and
seconds
Begin time 1,
end time 2
06 GdTm2Str Time 2 for grid
request in hours,
minutes and
seconds
Begin time 2,
end time 1
07 GdPwrStr Grid request
starting capacity
4.0 kW
08 GdPwrStp Grid request
disconnection
power limit
2.0 kW
09 GdStrChrgMod Charge start when
connecting to the
grid
Off off Equal
Full Full charge
Equal Equalization
charge
Both Full and
equalization
charge

Table of Contents