SMA America, LLC Assembly
Technical Description SI5048U-TUS121440 31
Observe the following conditions during mounting:
The mounting method and mounting location must be suitable for the weight and dimensions of
the Sunny Island.
Mount on a solid surface.
The installation location must be accessible at all times.
The ambient temperature must be between -13 °F (–25 °C) and 122 °F (+50 °C).
Do not expose the Sunny Island to direct sunlight to avoid power reduction (derating) due to
excessive heating.
Install the Sunny Island that way, that the display is at eye level in order to allow the operating
status to be read at all times.
Install vertically or tilted backwards by 45° max.
Never install the device with a forward tilt.
Do not mount in a horizontal position.
The connection area may not point upwards.
The room air can have a humidity of up to 100%, but this must not be condensing.
In a living area, do not mount the unit on
plasterboard walls etc. in order to avoid audible
vibrations.
The Sunny Island can make noises when in use
which can be considered a nuisance when installed
in a living area.