19 Parameter Lists SMA America, LLC
162 SI4548_6048-US-TB_en-13 Technical description
133# Generator State
No. Name Description Value clear text
(No.)
Explanation
01 GnDmdSrc Source for
generator request
None (1) No request
Bat (2) State-dependent battery
charging
Lod (3) Load-dependent
Tim (4) Time-controlled
Run1h (5) Requested for 1 hour
Start (6) Manually started
ExtSrcReq (7) Requested via an external
source
02 GnStt Generator state Off (1) Off
Init (2) Init
Ready (3) Waiting for request (ready)
Warm (4) Warming up
Connect (5) Connecting
Run (6) Operation
Retry (7) Restarting
Disconnect (8) Disconnecting
Cool (9) Cooling down
Lock (10) Locked after error
Fail (11) Error
FailLock (12) Locked after error occurred.
03 GnRmgTm Remaining time of
the generator
(minimum run time)
in hours, minutes
and seconds
04 GnRnStt Status generator
feedback on the
master
Off (1) off
On (2) on