22 Technical Data SMA America, LLC
228 SI4548_6048-US-TB_en-13 Technical description
Continuous AC power at 104°F (40°C) P
nom
4,700 W
AC power at 104°F (40°C) for 3 hours P
3h
5,000 W
Continuous AC power at 122°F (50°C) P
nom
3,500 W
Continuous AC power at 140°F (60°C) P
nom
2,200 W
Nominal AC current I
AC, nom
48.0 A
Maximum current (peak value) for 60 ms I
AC, max
180 A
Total harmonic distortion of the output voltage K
VAC
< 3%
Power factor cos φ –1 to +1
Input Data
Input voltage (adjustable) U
AC, ext
120 V (80 V to 150 V)
Input frequency (adjustable) f
ext
60 Hz ( 54 Hz to 66 Hz)
Maximum AC input current (adjustable) I
AC, ext
56 A (0 A to 56 A)
Maximum input power P
AC, ext
6.7 kW
Battery Data
Battery voltage (range) U
Bat, nom
48 V (41 V to 63 V)
Maximum battery charging current I
Bat, max
140 A
Continuous charging current I
Bat, nom
110 A
Battery capacity C
Bat
100 Ah to 10,000 Ah
Charge control IUoU procedure with automatic full
and equalization charge
Battery type VRLA / FLA / NiCd