EasyManua.ls Logo

SMA SUNNY ISLAND 6048-US - Page 170

SMA SUNNY ISLAND 6048-US
244 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
19 Parameter Lists SMA Solar Technology America LLC
170 SI4548-6048-US-BE-en-21 Operating Manual
#223 Battery Protection
11 BatTmpCps Battery
temperature
compensation
0 mV/C° to
10 mV /°C
VRLA 4.0 mV/
°C
FLA 4.0 mV/
°C
NiCd 0 mV/
°C
12 AutoEquChrgEn
a
Automatic
equalization
charge
Disable Disable Enable
Enable Enable
No. Name Description Value Default value
01 BatPro1TmStr Starting time of the
battery-preservation
mode (level 1)
22:00:00
02 BatPro1TmStp End time of the
battery-preservation
mode (level 1)
06:00:00
03 BatPro2TmStr Starting time of the
battery-preservation
mode (level 2)
17:00:00
04 BatPro2TmStp End time of the
battery-preservation
mode (level 2)
09:00:00
05 BatPro1Soc State of charge for
battery-preservation
mode, level 1
0% to 70% 20%
06 BatPro2Soc State of charge for
battery-preservation
mode, level 2
0% to 70% 15%
07 BatPro3Soc State of charge for
battery-preservation
mode, level 3
0% to 70% 10%
No. Name Description Value Explanation Default
value

Table of Contents

Other manuals for SMA SUNNY ISLAND 6048-US

Related product manuals