EasyManua.ls Logo

SMA SUNNY ISLAND 6048-US - Page 176

SMA SUNNY ISLAND 6048-US
244 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
19 Parameter Lists SMA Solar Technology America LLC
176 SI4548-6048-US-BE-en-21 Operating Manual
235# Generator Start
20 GnAlSns AI sensitivity Low Low Normal
Medium Medium
Normal Normal
High High
41 GnCurCtlMod Enable I-Loop in
generator mode
Droop (1) Standard
generator
operation without
I
-
Loop
Droop (1)
CurCtl (2) Current-controlled
generator
operation with
I
-
Loop
No. Name Description Value Explanation Default
value
01 GnAutoEna Generator autostart Off Disable On
On Enable
02 GnAutoStr Number of autostarts 3
03 GnSocTm1Str SOC limit for switching
on generator for time 1
40%
04 GnSocTm1Stp SOC limit for switching
off generator for time 1
80%
05 GnSocTm2Str SOC limit for switching
on generator for time 2
40%
06 GnSocTm2Stp SOC limit for switching
off generator for time 2
80%
07 GnTm1Str Time 1 for generator
request in hours,
minutes and seconds
Start: time 1, end: time
2
No. Name Description Value Explanation Default
value

Table of Contents