8 Commissioning SMA Solar Technology America LLC
74 SI4548-6048-US-BE-en-21 Operating Manual
8. Reconnect the conductors of the battery current sensor correctly as displayed in the graphic.
Make sure the insulated conductors have the correct polarity.
BatCur+ to terminal 1
BatCur– to terminal 2
9. Start the Sunny Island (see Section9.1 "Switching On", page75).
10. Check the current direction: "120.06 TotBatCur"
Current direction: Discharging the battery
No generator/utility grid connected
Loads are being supplied
The measured value of the battery current is positive.
Current direction: Charging the battery
Generator/utility grid connected
Loads are not/marginally supplied
Battery is being charged
The measured value of the battery current is negative.