Option 1
Metering + Auxiliary contacts Option
Available from third release 2004. This
option is factory fitted and includes a
specific metering display + metering
CTs to allow current + power metering.
Auxiliary contacts for 0,1,2 position,
padlock and Auto/Manual Mode.
Available from factory.
Verify there is no voltage
on the terminals before
mounting the options.
ATI 049 B GB
Contact f, g and h are closed when the
switch is in position 1, 2 or 0.
Contact i is closed when the switch is
in Automatic mode.
Contact j is closed when the switch is
padlocked.
Identification Terminals Type Feature Rating
f 13-14 Output Position 1 Auxiliary contact
or 20-21 Contact closed when
switch is in position 1
g 13-24 Output Position 2 Auxiliary contact
or 20-22 Contact closed when
switch is in position 2
h 13-34 Output Position 0 Auxiliary
or 20-23 contact Contact closed
when switch is in position 0
i 43-44 Output Auto/Manu information
or 24-25 Contact closed when
Automatic mode is active
j 53-54 Output Padlocking information
or 26-27 Contact closed when
the switch is padlocked
• Resistive load: 10 A • Inductive load: 3 A
Max Vac: 250 - Max operations: 5 x 10
7