SOCOMEC - Réf.: 678 623 G GB 35
ENGLISH
ENCLOSURES INSTALLATION (continued)
x1
1
1 / 2
2
GENERAL POINTS
For standard configurations, an RS
485 link is used to connect up to 31
ATI with a PC or a PLC over a distance
of 1500 metres, using JBUS/MOD-
BUS
©
protocol.
N° 1 N° 2 N° n
R = 120 Ω
1500 M
R = 120 Ω
Programmable
controllers
Other systems
N° 1
R = 120 Ω
RS485
0+- -+0
N° n
R = 120 Ω
1500 M 1500 M
Programmable
controllers
Other systems
repetor
DIRIS 109 BDIRIS 110 B
Recommendations:
You should use a shielded twisted pair
(LIYCY type). In a disturbed environ-
ment or large network (in terms of
length) we recommend the use of
2 shielded pairs (type LIYCY-CY). In
this case, one pair is used for the
+ and the –, and another pair, where
the 2 wires are short-circuited, for the
0V.
A repeater (1 channel) or an arrestor
(4 channels) should be used if you
intend to exceed the distance
(1500 m) and/or maximum number
(31) of ATI. Please contact us for
more information.
NB:
A 120 ohm resistance (found on the
additional module) must be fixed at
both ends of the link.
Other solutions are available (modem,
optical fibre, etc.). Please contact us.
A 3 minutes power off
action is required before
startup to allow option
recognition.
RS485 2 or 3 wires half duplex
Protocol JBUS/MODBUS
®
protocol/RTU mode
Speed 2400, 4800, 9600, 14400, 19200, 28800, 38400 Bauds
Galvanic insulation 4 kV (1 min 50 Hz)
Option 8
Communication module
Read paragraph communication for
instructions.
Installation of this module allows RS485
connection. Protocoles avaible are
JBUS/MODBUS
®
.
ATI 058 A GB