Identification Terminals Type Feature Rating
a 207 Inputs Common terminal
or 7
b 207-208 Input AT Timer inhibit input
or 7-8 Dry contact to close between terminals
7-8 to inhibit AT timer
c 207-209 Input Remote test on load input
or 7-9 Dry contact to close between terminals 7-9 to start
remotely a test on load (only
available in automatic mode)
d 210 or 10 (+) Power supply Power supply dedicated
to lightning option
207 or 7 (-) 5 Vdc < V
7-10 < 16 Vdc without load
9 Vdc < V7-10 < 10 Vdc for 1 to 2 inputs
e 73-74 Output Start Gen signal
or 11-12 30 V DC – 1 A
- Max direct voltage 30 Vdc
- Min direct voltage 10 Vdc
- Max inverse voltage 30 Vdc
- Galvanic insulation 3 kV
(1 min 50 Hz)
- Min pulse duration 1 s
- Max number of operations 10
8
CURRENT INPUTS (for METERING)
201 202 203 204 205 206
101102103104105106
1
3
N
2
1
3
N
2
Puissance 230 V AC - - Mesure de tension
Mesure de tension – OO – Puissance 230 V AC
R1 R2 S1 S2 T1 T2
R1 R2 S1 S2 T1 T2
I1 I2 I3
T2
T1
S2
S1
R2
R1
LOAD
R1 R2 S1 S2 T1 T2
R1 R2 S1 S2 T1 T2
R1 R2 S1 S2 T1 T2
R1 R2 S1 S2 T1 T2
Short circuit plug
delivered with the spare part
R1 R2 S1 S2 T1 T2
ATI 090 B GB
If the load is supplied, before discon-
necting the main connector, it is
necessary to short-circuit the secondary
of the current transformer (short-circuit
plug to be mounted).