SOCOMEC - Réf. : 678 623 G GB 77
ENGLISH
COMMUNICATION (continued)
SAVED COMMAND (RESET)
The following command should be
done to save programming parame-
ters changes for ATI number 5.
NB:
ATI will not reply
to this command.
Slave
05
Function
06
High-order
address
06
Low-order
address
00
Values
0000
CRC 16
88C6
Diagnostic zone
Decimal Hexa Number Variable
Address Address of words
257 101 1 Product Identification Standard version 1239
Metering version 1241
258 102 1 Slot Ident Option 1 available option
0 communication option
Option of slot 1
0xFF no option
0x20 Main/Gen
259 103 1 Slot Ident Option 2 available option
0 communication option
Option of slot 2
0xFF no option
0x20 Main/Gen
260 104 2 Reserved
262 106 1 Version soft version of product
263 107 2 Serial number serial number
265 109 17 Reserved
278 116 1 Motor Mode 3 stable states
Bit3 Bit2 Bit1 Bit0
1010 Auto
1001 Padlock
0110 Manu
282 11A 1 Switch State 3 stable states
Bit2 Bit1 Bit0
0 0 1 Position 1
0 1 0 Position 0
1 0 0 Position 2
283 11B 2 Reserved
285 11D 1 CounterMainGen Counter number of transfer
286 11E 1 Gen relay state 2 stable states
Bit1 Bit0
1 0 relay stopped
0 1 relay started