A
A
623
600
1175
200
775
720
520
30
28
80
50
50
80
536
480
50
120
14
14
536
480
1375
Torque: M10 26Nm (Max)
M12 45Nm (Max)
Phase and neutral cable
800A:3x240mm
2
or 2x300mm
2
(Max)
1000A:4x240mm
2
or 2x300mm
2
(Max)
Earth cable:
-800A:2x120mm
2
or 1x300mm
2
(Max)
-1000A:2x240mm
2
or 1x300mm
2
(Max)
A-A
Main
Load
Generator
14 SOCOMEC - Réf. : 678 623 G GB
800A/1000 A ratings
Power Cables Connection
ATYS 127 A GB