36 SOCOMEC - Réf.: 678 623 G GB
VOLTAGE CONFIGURATIONS
VOLTAGE OPTIONS
Standard 230Vac +/- 20%
50 Hz 3 phase 4 wires - 3P4L 60 Hz 3 phase 4 wires – 3P4L
Star connections Star connections
FG Wilson Voltage FG Wilson Voltage
option code option code
V502 415/240V V603 440/254V
(2)
V503 400/230V V605 380/220V
V504 380/220V V608 220/127V
V507 220/127V V610 208/120V
(3)
V510 200/115V
(1)
V611 240/139V
(1): +20%/-12%
(2): +13%/-20%
(3): +20%/-15%
50 Hz 3 phase 3 (4) wires - 3P3(4)L 60 Hz 3 phase 3 (4) wires – 3P3(4)L
Delta connections Delta connections
V506 230/115V V606 240/120V
V508 220/110V V607 230/115V
V609 220/110V
50 Hz single phase 3 wire – 1P3L 60 Hz single phase 3 wire – 1P3L
V522 240/120V V622 240/120V
V524 230/115V V624 230/115V
V526 220/110V V626 220/110V
50 Hz single phase 2 wire – 1P2L 60 Hz single phase 2 wire – 1P2L
V521 240V V621 240V
V523 230V V623 230V
V525 220V V625 220V
Optional 277 Vac (+/-20% for rating below 630 A, +20/-15% for rating
800 A and above)
50 Hz 3 phase 4 wires - 3P4L 60 Hz 3 phase 4 wires – 3P4L
Star connections Star connections
FG Wilson Voltage FG Wilson Voltage
option code option code
V601 480/277V
To meet all voltages required by the market, 2 ATI versions have been developed:
CABLE CONNECTIONS BETWEEN SWITCH
AND ELECTRONIC MODULE
A voltage sensing kit is used to provide
sensing and power connections from
the switch terminals to the electronic
module terminals.
The ATI enclosures are delivered as
standard for 3 phases 4 wires applica-
tions, 400/230 Vac nominal voltage.
In some 3 phase 4 wires, all 3 phases 3
wires, or single phase 2 or 3 wires
applications, sensing connections keep
the same, but power connections must
be modified according to guidelines
included before connection diagrams.
In standard ATI (bottom
entry) generator cable is
red and main cable is black.
In top entry ATI main cable
is red and generator cable
is black.