SOCOMEC - Réf.: 678 623 G GB 45
ENGLISH
BASIC PRODUCT USE (continued)
The setup menu integrates 5 parame-
ters described in the table hereunder.
The table explains parameters’ definition,
settings possibilities, and default values.
Press Down push button to access parameter required.
Press Up push button to come back to previous value, or press
or Home push button to come back to
.
SETUP MENU
Un: Phase-Phase
nominal voltage.
From 200 to 480 V 400 V AC
nt: Network configuration.
Type of metering
(1P or 3P phases).
Number of active wires
(2L, 3L or 4L)
definition.
1P2L, 1P3L, 3P4L 3P4L
3P3L, 1PAP
Fn: Nominal frequency.
50 or 60 Hz 50 Hz
trI: Retransfer inhibit feature:
press on RTI button required to
allow retransfer from gen to
main.
Yes or No No
Crs: Reset number of commutation
counter (from Main to Gen).
Displays no once reset.
Yes or No No
Definition Setting range Default value
Parameter Display
ATI 073 A