EasyManua.ls Logo

socomec ATI 800 A - Manual Mode

socomec ATI 800 A
88 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SOCOMEC - Réf.: 678 623 G GB 53
ENGLISH
BASIC PRODUCT USE (continued)
To access Manual Mode turn the front
keyswitch to manual position.
Take the handle, attached to the chain,
on the right side of the enclosure, to
manually operate the switch.
Verify the switch position on the front
position label before any manual
operation.
from Position 1 turn clockwise to
reach position 0
from position 0 turn clockwise to
reach position 2
from position 2 turn anti clockwise
to reach position 0
from position 0 turn anti clockwise
to reach position 1
MANUAL MODE
Manual operation
Padlock is only possible in manual
position.
handle must be out of its housing to
padlock
• padlock is possible in position 0, 1, 2.
Manually pull the padlock handle to
allow padlock insertion in the hole.
Padlocking
Once in manual mode it is possible:
To access programming and
visualisation menus
• To padlock the switch
To operate the switch with the handle
To start the Gen using test off load
pushbutton.
Manual mode operation
Programming Visualisation Padlocking
Handle
Operation
Start Generator
(Test off Load)
MANUAL MODE
Do not force the product
Do not leave the manual
handle in automatic mode.