74 SOCOMEC - Réf. : 678 623 G GB
COMMUNICATION
The JBUS/MODBUS
®
used by the ATI
involves a dialogue using a master-
slave hierarchical structure. There are
two possible dialogues:
the master communicates with a
slave (ATI) and waits for its reply
the master communicates with all the
slaves (ATI) without waiting for their
reply.
The mode of communication is the
RTU (Remote Terminal Unit) using
hexadecimal characters of at least 8
bits.
According to the JBUS/MODBUS
®
protocol, transmission time must be
less than 3 silences, i.e. the emission
time of 3 characters so that the mes-
sage is processed by the ATI.
To correctly use information, the
following functions are important:
3: to read n words (maximum 128).
6: to write one word.
8: to diagnose exchanges between
the master and the slave via
meters 1, 3, 4, 5 and 6.
16 : to write n words (maximum 128).
LIST OF PARAMETERS TO BE DISPLAYED (FUNCTION 3)
Table of values on 2 words
The standard communications frame
consists of:
Slave address Function code Address Data CRC 16
NB:
When selecting slave address 0, a
message is sent to all the instruments
present on the network (only for func-
tions 6 and 16).
Comment:
The maximum reply time is 250 ms.
Decimal Hexa Number
Address Address of words Variable Units
768 300 2 I1 A/100
770 302 2 I2 A/100
772 304 2 I3 A/100
774 306 2 In A/100
776 308 2 U12Main V/100
778 30A 2 U23Main V/100
780 30C 2 U31Main V/100
782 30E 2 V1Main V/100
784 310 2 V2Main V/100
786 312 2 V3Main V/100
788 314 2 Freq.Main Hz/100
790 316 2 Active power (total) kW/100
792 318 2 Reactive power (total) kVar/100
794 31A 2 Apparent power (total) kVA/100
796 31C 2 Power factor 0,001
880 370 2 U12 Gen V/100
882 372 2 U23 Gen V/100
884 374 2 U31Gen V/100
886 376 2 V1Gen V/100
888 378 2 V2Gen V/100
890 37A 2 V3Gen V/100
892 37C 2 FreqGen Hz/100
894 37E 1 1MT V/100
895 37F 1 2MT V/100
896 380 1 AT s
897 381 1 DBT s
898 382 1 ROT s
Example
:
To read U31 gen = 228,89, the
following message should be sent: