ATySController C25 - 549780A - SOCOMEC
16. ANNEXE II MODBUS COMMUNICATION ADDRESS
AND DESIGNATION DETAILS
All communication addresses, except communication parameters (4) are read only RO (read function 03/04).
The communication protocol adopts the standard MODBUS-RTU protocol, with master-slave acknowledgment
connection (half duplex).
As standard the baud rate is set to 38400, parity bit to 1 (these settings can be modied through Modbus).
When the product is communicating the COM Led will blink.
16.1. Input / Output state
Dec. Address Word count Description Unit
10008 1 Position I input state (70-71) : 0 : OFF
1 : ON
10009 1 Position II input state (70-72) : 0 : OFF
1 : ON
10010 1 Position 0 input state (70-72) : 0 : OFF
1 : ON
10011 1 Fire Input state (F1-F2): 0 : OFF
1 : ON
10012 1 CTRL inhibit (63A-64A) 0 : Inhibit
1 : Automatic
10022 1 Genset control output: (51-52-54) 0 : Genset start order OFF
0 : Genset start order ON
10023 1 Control signal output I (15-17): 0: Output not activated
I : Output activated
10024 1 Control signal output II (16-17): 0: Output not activated
I : Output activated
10025 1 Control signal output I (15-17): 0: Output not activated
I : Output activated
10026 1 Control signal output I (15-17): 0: Output not activated
I : Output activated
10120 1 I position state : 0 : OFF
I : ON
10121 1 II position state : 0 : OFF
I : ON
10123 1 0 position state : 0 : OFF
I : ON
16.2. Status
Dec. Address Word count Description Unit
10124 1 Source 1 power status 0 : OFF
1 : ON
10125 1 Source 2 power status 0 : OFF
1 : ON
10040 – 10071 32 Alarms 01-32 : 0 : No alarm
1 : Alarm
40005 1 C25 operating mode (1-4): 2 : Manual
3 : Automatic
4 : Test