38
EN
ATySController C25 - 549780A - SOCOMEC
16.3. Voltage sensing
Dec. Address Word count Description Unit
10192 1 Source 1 L1-N voltage value (V)
10193 1 Source 1 L2-N voltage value (V)
10194 1 Source 1 L3-N voltage value (V)
10195 1 Source 1 L-N average voltage (V)
10196 1 Source 1 L1 –L2 voltage value (V)
10197 1 Source 1 L2 –L3 voltage value (V)
10198 1 Source 1 L3 –L1 voltage value (V)
10199 1 Source 1 L-L average voltage (V)
10204 1 Source 1 frequency (0.1 Hz)
10205 1 Source 2 L1-N voltage value (V)
10206 1 Source 2 L2-N voltage value (V)
10207 1 Source 2 L3-N voltage value (V)
10208 1 Source 2 L-N average voltage (V)
10209 1 Source 2 L1 –L2 voltage value (V)
10210 1 Source 2 L2 –L3 voltage value (V)
10211 1 Source 2 L3 –L1 voltage value (V)
10212 1 Source 2 L-L average voltage (V)
10217 1 Source 2 frequency (0.1 Hz)
16.4. Communication parameters
Dec. Address Word count Description Unit
40017 1 C25 communication node address: 1-247
40018 1 Baud rate : 2 – 2400
3 – 4800
4 – 9600
5 – 19200
6 – 38400
40019 1 Serial Data format : 1-5 1- 8N
2 – 80
3 – 8E
4 – 70
5 – 7E
40020 1 Stop bit: 1 – 2
As standard the baud rate is set to 38400, parity bit to 1, Modbus address 3 these parameters can be changed
using the write function 10.
Once the conguration is done, write data 1 at address Dec. 40565. After changing the parameters the product
buzzer will sound twice and the Com LED will stay on.
To reset to default parameters press the RES button for 30 seconds, the product will reboot and the standard
communication settings will be set.
16.5. Maintenance
Dec. Address Word count Description Unit
10126 2 Position I operation count in AUTO mode: 0-60 000
10128 2 Position II operation count in AUTO mode: 0-60 000
10130 2 Position I operation count in Manual mode: 0-60 000
10132 2 Position II operation count in Manual mode: 0-60 000
10170 -10179 8 Serial number (V)
10186 1 Hardware version (V)
10187 1 Software version (V)