STEP 2: Fixing the controller on the backplate
Drill mounting holes in the backplate to match the xing holes as shown and indicated below. Fix the controller through the
mounting legs to the backplate with a maximum screw diameter of 6mm/0.22in.
5.9
+/-0.4
150
+/-1
6.77 - 7
172 - 178
Mounting of Digital I/O extension modules (Accessory for C65 only):
Digital I/O modules are accessories not delivered with the product. These optional modules can be ordered using the
references below:
IO input/output modules
DIRIS Digiware IO-10
Digital inputs/outputs
DIRISDigiware IO-10
Ref. 48290140
Digital I/O modules provide additional inputs /outputs to be used with/by the ATyS C65.
The maximum length of the digiware bus is 100 meters.
CAUTION ! The maximum number of I/O optional modules that can be added through the Digiware bus to
the controller is 6; this is equivalent to 24 digital inputs and 12 digital outputs.
In order to use the I/O modules the 24VDC input of the C65 controller must be supplied with 24 VDC.
LATCHING RELAY OUTPUTS (NC-NO-C)
INPUTS/ENTRÉES
OUTPUT RELAYS (NC-NO-C)
OUT 5OUT 6 OUT 4 OUT 3 OUT 2 OUT 1
12 14 1122 24 2132 34 3142 44 4152 54 5162 64 61
C IN6 IN5 IN4 IN3 IN2 IN1
70 76 75 74 73 72 7181 82
ATyS C65
Optional
Aux. Supply
24V (6W)
ATSE Controller
Config
USB
BATTERY
PILE
BR2032 LITHIUM
RS485
NC
MADE IN
FRANCE
L2 L3 NL1 L2 L3 NL1
ON
OFF
120Ω
IN I3 I2 I1
GND GND
CURRENT TRANSFORMERS : 1A or 5A
TRANSFORMATEURS DE COURANT : 1A ou 5A
SOURCE S2 SOURCE S1
An end-of-the-bus resistor is necessary for a correct communication between the modules and the controller: