27
EN
ATySController C55/65 - 549866C - SOCOMEC
10. FIRST POWER UP – SMART WIZARD
Once the controller is connected to the switch with the cable harness, as soon as the controller is powered up, it will
automatically start in MANUAL mode and, in order to facilitate the commissioning, a smart wizard will appear to drive the user
through the main conguration parameters.
Language Source configTime & date
Switch &
Application
Product Name Communication
The rst out of 8 questions will be the language. User can choose between the following 9 languages:
English
French
German
Italian
Polish
Spanish
Turkish
Chinese
Portuguese
Then it will follow the option to start the wizard with the following options:
Start now (will start the assisted conguration now).
Remind me the next power on (will prompt user to go through the conguration during the next controller power up).
Never ask me again (will not prompt user again).
The wizard will always be accessible anyway in "MAIN MENU" > "PARAMETERS" > "WIZARD" in case it is missed the rst time.
If "NOW" is selected, then the options are:
To use the smart conguration: parameters like voltage, frequency and phase rotation will be auto detected and user will
be able to validate or modify the detected values.
To use the manual conguration: user will enter manually all network conguration values.
The controller will require the congurator 4-digit password before the conguration (by default, 1000).