14. CONFIGURATION
The conguration on the ATyS C55/65 can be done:
- Directly on the HMI.
- By USB connection to the controller (using EasyCong software, available for free download
at www.socomec.com).
- Through communication (DIGIWARE or RS485).
Note: The conguration can be done even without cabling the AC or DC supply to the controller, only connecting
it to a computer with an USB cable. The controller will use the USB to power up the screen, buttons and main
functions, permitting the conguration through any of these methods.
For safety reasons, if the controller is connected to the switch, it is strongly recommended to congure in Manual or
Inhibit mode.
14.1. Conguration through the display
How to congure the main parameters manually using the display:
PARAMETERS MENU
Inside the PARAMETERS menu of the Main Menu (accessible by entering the Congurator password, by default 1000) all the
main parameters of the controller can be set:
NETWORK Conguration of the nominal voltage and frequency, the phase rotation, the type of switch and the
sources priorities, as well as the operating range where the controller will consider a source as
available. See chapter "NETWORK parameters menu", page 47
LOAD Conguration of the nominal current and the transformers used to measure the current on the load
side of the switch. See chapter "LOAD parameters menu (only C65)", page 53.
DISPLAY Conguration for language, date&time. The test button use (“LOAD TEST” or “NO LOAD TEST”)
and X&Y LED conguration (C65 only). Product name and screensaver text. See chapter "DISPLAY
parameters menu", page 54.
TIMERS Conguration for operational timer. See chapter "TIMERS parameters menu", page 56.
I/O Conguration of the Inputs and Outputs of the controller and the external I/O modules.
See chapter "I/O parameters menu", page 58.
COMMUNICATIONS Conguration of the communication parameters such as the Modbus address or the baudrate but
also the use of the RJ45 outputs (Only on ATyS C65). See chapter "COMMUNICATION parameters
menu", page 59.
ALARMS Permits programming different alarm types that can be linked to outputs and will show the
information on the screen of the ATyS C65 and on the webserver (only available with M70 or D70
gateways). See chapter "ALARMS parameters menu", page 63.
PASSWORDS Permits changing the passwords for the different users. See chapter "PASSWORDS", page 67.
WIZARD Allows user to go through the wizard conguration again.
Important Note: when doing the conguration through the display, do not forget to put the controller in
AUTO mode after the conguration is over to start the AUTOMATIC mode.