ATySController C55/65 - 549866C - SOCOMEC
14. CONFIGURATION
The conguration on the ATyS C55/65 can be done:
- Directly on the HMI.
- By USB connection to the controller (using EasyCong software, available for free download
at www.socomec.com).
- Through communication (DIGIWARE or RS485).
Note: The conguration can be done even without cabling the AC or DC supply to the controller, only connecting
it to a computer with an USB cable. The controller will use the USB to power up the screen, buttons and main
functions, permitting the conguration through any of these methods.
For safety reasons, if the controller is connected to the switch, it is strongly recommended to congure in Manual or
Inhibit mode.
14.1. Conguration through the display
How to congure the main parameters manually using the display:
PARAMETERS MENU
Inside the PARAMETERS menu of the Main Menu (accessible by entering the Congurator password, by default 1000) all the
main parameters of the controller can be set:
NETWORK Conguration of the nominal voltage and frequency, the phase rotation, the type of switch and the
sources priorities, as well as the operating range where the controller will consider a source as
available. See chapter "NETWORK parameters menu", page 47
LOAD Conguration of the nominal current and the transformers used to measure the current on the load
side of the switch. See chapter "LOAD parameters menu (only C65)", page 53.
DISPLAY Conguration for language, date&time. The test button use (“LOAD TEST” or “NO LOAD TEST”)
and X&Y LED conguration (C65 only). Product name and screensaver text. See chapter "DISPLAY
parameters menu", page 54.
TIMERS Conguration for operational timer. See chapter "TIMERS parameters menu", page 56.
I/O Conguration of the Inputs and Outputs of the controller and the external I/O modules.
See chapter "I/O parameters menu", page 58.
COMMUNICATIONS Conguration of the communication parameters such as the Modbus address or the baudrate but
also the use of the RJ45 outputs (Only on ATyS C65). See chapter "COMMUNICATION parameters
menu", page 59.
ALARMS Permits programming different alarm types that can be linked to outputs and will show the
information on the screen of the ATyS C65 and on the webserver (only available with M70 or D70
gateways). See chapter "ALARMS parameters menu", page 63.
PASSWORDS Permits changing the passwords for the different users. See chapter "PASSWORDS", page 67.
WIZARD Allows user to go through the wizard conguration again.
Important Note: when doing the conguration through the display, do not forget to put the controller in
AUTO mode after the conguration is over to start the AUTOMATIC mode.