EasyManua.ls Logo

socomec ATyS C55 - TIMERS parameters menu

socomec ATyS C55
110 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
56
EN
ATySController C55/65 - 549866C - SOCOMEC
14.1.4. TIMERS parameters menu
All the operational timers can be set on this menu. They are up to 26 general timers splitted into 4 groups:
Note: the timers linked to specic functions are not included in this chapter. Consult the Timers Annex in chapter
"Annex 16 - 2. Timers list", page 88 to have the full list.
14.1.4.1. Operation timers
FAILURE TIMER (s): time after source is lost, to make sure it’s really lost and start a transfer.
RETURN TIMER (s): time after a transformer/main source that was off comes back, to make sure it really came back.
AVAILABLE TIMER (s): time for a genset/diesel generator source to be on and inside the right dened values to be
considered available and ready to accept a transfer.
S1 DEAD BAND (s): time to wait without load supply (including source failure time and time in center-off / zero position)
when transfering from S1 to S2.
S2 DEAD BAND (s): time to wait without load supply (including source failure time and time in center-off / zero position)
when transfering from S2 to S1.
Note: by default, S1 and S2 DEAD BAND are the same and set to 3s. On C55 there is no differentiation between
S1 or S2. For ATyS FT technology (I-II switch, with no 0 position), DBT timer does not exist.
Note: see "Annex 16 - 5. Operating sequences", page 96 for operational timer graph and see TIMER Annex for
more details on congurable values for these timers
14.1.4.2. Genset source 1/2 timers
Note: if the source is not linked to a genset the following message will be shown:
- Genset source 1 and source 2 are available if the source is related to a genset (in M/G depending on priority, and in G/G).
GENSET COOLDOWN (s): This timer will count down once the load leaves the source with a genset, when this timer
expires the genset start signal linked to this source will be deactivated. This timer is used to cool-down the genset before
shutting it down.
START TIMEOUT (s): Maximum time for the genset to start. After this time, a fault will pop-up saying “Fail to start genset”.
This timer must be greater than the source "AVAILABLE TIMER" or the genset will always be concidered as fail to start.

Table of Contents

Other manuals for socomec ATyS C55

Related product manuals