60
EN
ATySController C55/65 - 549866C - SOCOMEC
14.1.6.2. Communications Menu
The ATyS C55 and C65 have RS485 communication by default using MODBUS RTU protocol. Inside the communication
menu the main parameters to make that communication effective can be set.
- MODBUS ADDRESS: By default 6, any value between 1 and 247 can be used.
- RS485 MODBUS: All Modbus parameters can be set here:
BAUDRATE (1200-2400-4800-9600-19200-38400-57600-115200) By default 38400.
STOP: (1BIT – 2BITS) By default 1 BIT
PARITY: (ODD-EVEN-NONE) By default none
- DIGIBUS COMM: The same parameters than for RS485 can be set also for the Digibus connection (RJ45 inputs on ATyS
C65) when integrated in a DIRIS Digiware system.
- DIGIWARE MODE: to be able to use the controller inside a Digiware chain, it’s needed to change the parameter MODE
to SLAVE. To be able to use external I/O modules the function of the RJ45 has to be switched to “MASTER OVER I/O”
changing the MODE parameter: