78
EN
ATySController C55/65 - 549866C - SOCOMEC
15.2. Faults management and Troubleshooting
There are several events that can cause a Fault on the controller. Unlike the alarms, the faults are not user-selectable, they will
always be considered and actions will take place as follows:
FAULT
DESCRIPTION
(CAUSE)
ACTIONS
ACKNOWLEDGE
/ CLEARED
FAULT
LOG
POP-UP
FAULT
LED
OUTPUT
Unexpected
Transfer
The controller receives a
feedback/return from the
switch without sending
any order (auto or manu).
Also if loss feedback of
current position.
Mode stays the
same.
Can also be
cleared through
display or through
RST - Reset Fault
input.
Yes
Yes,
"Unexpected
Transfer"
BLINKS
(priority)
FLT - Fault active
Failed to
Transfer
Position not reached
after an order sent by
controller (auto or manu)
or loss of feedback of the
new source after sending
a transfer command.
Mode stays the
same. Controller
will start retries.
Automatically
cleared if the
requested position
is reached or
cleared through
display or through
RST - Reset Fault
input.
Yes
Yes, "Failed to
transfer"
BLINKS
(priority)
FLT - Fault active
Max
operation
per minutes
reached
If the controller performs
10 operations in less
than 1 minute (by default)
(automatic or controlled/
manual)
Mode stays the
same. During
a timer, the
controller will not
do or allow any
operation.
Automatic after
the 1 minute
(configurable
through software)
(value is dynamic).
Yes
Yes, "Max
operations
per minutes
reached"
FIXED
(non-critical)
FLT - Fault active
Max
password
attempts
reached
User tries to enter a
profile password more
than X times set in the
maintenance menu (by
default 10 attempts)
Mode stays
the same.
Can't enter any
password during
X time set in the
maintenance
menu (by default 2
minutes)
Automatic after
the set timeout
(maintenance
mode).
Yes
Yes, "Max
number of tries
reached, please
wait: X s"
FIXED
(non-critical)
FLT - Fault active
Genset
Failstart
Controller tries to start
a genset (as configured)
and after the genset start
delay, the genset doesn't
start (controller doesn't
see the source on)
Mode stays the
same. Genset
start relay remains
active unless other
source is available.
Automatic if
genset starts or
if source is set as
Main/Utility.
Yes
Yes, "Engine fail
to start"
BLINKS
(priority)
FLT - Fault active
External
fault
If an input is selected as
FTE - External Fault and
becomes active
Switch goes
to position 0 /
center-off directly
without timers and
the mode is set
to Partial Inhibit
(genset starts if
needed).
Input mustn't be
active and reset by
user is requested
(by RST- Reset
Fault input or
through display.
Yes
Yes, "External
fault"
BLINKS
(priority)
FLT - Fault active
Unknown
position
Loss of switch position
input while no order
was given or no position
feedback after the start of
a transfer
Mode stays the
same
Auto-cleared if any
position becomes
active
Yes
Yes, "Unknown
position"
BLINKS
(priority)
FLT - Fault active
For faults with pop-up, the pop-up will be cleared when fault will be cleared or by pressing any button on the front face of the
controller. The total number of faults logged on the controller is dynamic, as the total number of “faults + alarms” is 100 (not
including the events, which are 3000 on C65 and 300 on C55) and uses a FIFO ordering.