79
EN
ATySController C55/65 - 549866C - SOCOMEC
To clear Faults through the display, it is possible inside the LOG/FAULTS menu with the option “PRESS OK TO CLEAR
FAULTS”, using the congurator prole password. There is also a shortcut by holding the button for 1,5s and validating
on the pop-up that appears. If the fault is still active, it will be inside the log “in progress” but the fault LED and output will be
off. I the faults are not active any more, they will be logged in the “history” log. This way to clear the fault will be automatically
proposed by the controller through a pop-up:
15.3. Maintenance of the controller
To clean the front face of the equipment, use a soft cloth with water and non-abrasive liquids.
The ATyS C55/C65 controller is conceived to be a maintenance free, t and forget unit. However, it is recommended to
perform visual inspections periodically on the device, checking the connections, that the display screen is functional and
the LED using the lamp test button and ensuring the correct functioning with the switching device and with any possible
associated software.
As a best practice, perform at least one full cycle with your equipment (solution with the controller + RTSE) every year.
There are no serviceable parts in the controller. In case of a malfunction, don't hesitate to contact Socomec and/or return
the product for a replacement in case warranty is still valid. During conversations with Socomec, you might be asked for
the model, rmware version or the serial number of the unit. This information can be found inside the ABOUT menu. If the
controller screen is not functional, then use the labels and QR code on the back side of the controller to inform our service
team.
RTC Battery replacement
Depending on the working and environmental conditions conditions the battery will need to be replaced when the controller
displays a message "RTC Low Battery". Should the time & date at power up be incorrect it will be time to replace the battery.
To do so:
1. Disconnect all terminals from the controller
2. Release the cover on the side of the controller containing the battery
3. Remove the old battery with an apropiate plastic tool
4. Place the new battery on the correct side (polarity) in the holder from the pcb and push with the nger until it reaches
the position of the old one.
5. Put back the plastic cover on the side of the controller and pressure slightly until it perfectly ts.
6. Connect back the terminals to the controller
7. Power up and adjust time and date
For battery replacement, use a BR2032 coin-type cell.