TRIGRAM INPUT NAME DESCRIPTION C65 C55
PS0 GO TO POS.0
External order to go to pos 0
Position command only available if the mode is in position CTRL. Command 0
has priority over commands I and II.
x x
RT0 RETURN TO 0 Overrides the "Return to 0" function inside SPECIFIC FUNCTIONS x -
BLK BLOCKED
Product blocked, meaning that the RTSE is blocked, can't move. The
controller will go into Partial Inhibition (starting the genset if necessary) but not
transfering. Message on the display "Product blocked"
x x
TP1 TRIP BRK1 Protection on S1 has tripped x x
TP2 TRIP BRK 2 Protection on S2 has tripped x x
REC AUTO/MANU
Places the controller in manual mode remotely (can be used to activate the
use of inputs "go to position X").
x x
EST EMERGENCY SIGN.
Emmergency off signal. Controller will pilot to go to position 0 (if any). CTRL
will be disabled, AUTOMATIC mode will be off, genset won't be started,
"Emergency Off" will be displayed on screen. If Lift/Elevator signal is enabled,
its timers will be respected before giving the command to go to 0.
x x
IPI IN-PHASE INHIBIT
In-phase transfer inhibition:
This input will disable the in-phase transfer function, so if the input is active it
will disable the in-phase transfer between sources, allowing a transfer without
taking into account the phase monitoring between sources.
x -
IPB IN-PHASE BYPASS
In-phase bypass:
When this input is active (pulse), the switch will bypass the dwell time reset
timer (sync-checking). This input can only be used when there is a in-phase
checking already taking place.This input can only be taken into account
after the In-phase delay timer is elapsed (DWELL TIMER RESET / IN-PHASE
RESEARCH)DELAY.
x -
BCT BYPASS TIMER
Bypass timer:
Bypasses the current timer on the screen / rst one of the list of timers running.
x x
ELB LOAD CTRL BYPASS
It will bypass the load control delay timer (ELD) when active, if the elevator
function is active.
x -
IS1 INHIBIT S1
Inhibits source 1. Transfer to the source is forbidden and if the load is on that
source it will immediately be transfered to the opposite
x -
IS2 INHIBIT S2
Inhibits source 2. Transfer to the source is forbidden and if the load is on that
source it will immediately be transfered to the opposite
x -
CH1 BREAKER 1 CHARGED Gives feedback that the breaker mechanism is charged and ready to transfer. x x
CH2 BREAKER 1 CHARGED Gives feedback that the breaker mechanism is charged and ready to transfer. x x
CTT COMMIT Activate the commite to transfer function when this input is active. x -
EGG BACKUP GENGEN Activates the backup Gen-gen mode if the application is set to "GEN-GEN" x x
CYC CYCLER Activates the cycler function x x
DIS1 BRK1 DISCONECTED
Informs the controller that the breaker 1 is disonnected. When activated a
pop-up will apear on the screenand automatic operation will be inhibited.
x x
DIS2 BRK2 DISCONECTED
Informs the controller that the breaker 2 is disonnected. When activated a
pop-up will apear on the screenand automatic operation will be inhibited.
x x
MS1 MTSE in position 1
Only for bypass technology indicates the the manual bypass switch is in
position 1
x -
MS0 MTSE in position 0
Only for bypass technology indicates the the manual bypass switch is in
position 0
x -
MS2 MTSE in position 2
Only for bypass technology indicates the the manual bypass switch is in
position 2
x -
WTH Withdrawn Only for bypass technology, indicates that the RTSE is withdrawn x -
CON Connected Only for bypass technology, indicates the the RTSE is connected x -