TRIGRAM OUTPUT NAME DESCRIPTION C65 C55
ROS (EXT) TEST ON LOAD This output is activated if any load test (either HMI or remote order) is ongoing. x x
PTS SMART SHEDDING
Output active while the smart load shedding is active. To work, the "Smart Load
Shedding" fucntion has to be enabled inside the Specic functions menu.
x -
EES BATTERY CHARGER
Output to activate the battery charging. It is linked to the battery charger tim-
mers.
x -
TPP TRIP PARTIAL Report of protection tripping in one of the sources. x -
TPT TRIP TOTAL Report of protection tripping on both sources. x -
IPT IPT IN PROGRESS In Phase Transfer ongoing. x -
CO1-CO6 COPY INPUT x Active when the corresponding input will be active x -
EEA SCHEDULER ACTIVE
This output will be active while any of the programs for the Engine exerciser
are active. The settings of the exerciser parameters can be congured in the
dedicated menu.
x -
ELV LOAD CONTROL
Load control signal output. It should be linked to the load in order to load shed
before transferring and reactivate the load after transfer.
x -
ARO ALARM REPORT
This alarm output will be active in the case that one of the alarms set in the
Alarms menu is active and the option to use the output to report the alarm is
enabled.
x x
DCT HVAC COMPRESSOR
When going back to principal source position the contact will become active
prior to starting the transfer (to shut down the compressor), then the transfer
will take place and then after reaching the opposite source, a timer dened in
the specic functions menu will elapse before deactivating this output again. It
avoids stressing the compressors in HVAC chillers.
x -
- NONE OUTPUT NOT USED x x
GS1 GENSET S1 START
Genset start/stop output. Only available on OUT 5 when the source is a genera-
tor (when congured as Genset/Genset) or on OUT 6 (when congured as Main/
Genset with priority on S2).
x x
GS2 GENSET S2 START
Genset start/stop output. Only available on OUT 6 when the source is a gene-
rator.
x x
AUD CRIT. ALM. ACTIVE Output active when an alarm with the criticity CRITICAL is active
x x
PHI PHASE INVERSION
Output activated if the phase rotation measured is different from the one
configured in APPLICATION
x -
OD1-OD7 ON DELAY Outputs linked to the "on delay timers"
x x
ARO ALM REPORT Reports the alarm configured in the alarm menu.
PRL bypass
Bypass only, output report to signal that the bypass is in parralel mode
(bypass and ATSE active).
x -
TST bypass Bypass only, output report to signal that the bypass is in test mode.
x -
EMG bypass
Bypass only, output report to signal that the bypass is bypassed by
emergency manual switch.
x -
NRM bypass
Bypass only, output report to signal that the bypass is bypassed by nomal
manual switch.
x -
Note: position orders cannot be used with the OUT 5 and OUT 6 (latching relays).
The latching relays can take up to 2 seconds between opposite orders (NO to NC or NC to NO) and for added
security when starting a genset will change state based on the timers or when the backup power is exhausted.