ATySController C55/65 - 549866C - SOCOMEC
Annexe 16 - 5.2. MAIN-MAIN Applications
Loss of source 1?
yes
Failure Timer
Pop-up alarm &
continue searching
yes
In-phase timer is
over?
no
yes
Source 2 Available? GO TO CENTER-OFF
Parameters in the window
during Dwell time reset?
yes
no yes
no
ENGINE START
(GEN)
no
Go to 0 active? (DT)
Inhibit/Bypass
Inphase?
yes
Source 2 Available?
no
Alarm FAIL
START (GEN)
In-phase timer (dwell
time) start
yes yes
no
Availability Timer
In-phase Transfer
enabled?
no
Delayed
Transition? (DT)
no
Retransfer
autorization
yes
yes
Go to CENTER-OFF
Source 1 and 2 are
lost?
Dead band timer
yes
GO TO SOURCE 2
Engine Cool Down
Timer
GO TO SOURCE 1
Dead band Timer
Go to CENTER-OFF
yes
Delayed Transition?
(DT)
no
Manual retransfer
active?
yes
Return Timer
yes
Source 1 is back?
Engine Cool Down
Timer
GO TO SOURCE 1
Dead band Timer
Go to CENTER-OFF
yes
Delayed Transition?
(DT)
no
Manual retransfer
active?
yes
Return Timer
yes
Source 1 is back?