EasyManua.ls Logo

socomec ATyS C55 - Technical Characteristics

socomec ATyS C55
110 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
98
EN
ATySController C55/65 - 549866C - SOCOMEC
Annex 16 - 6. ATyS C55/C65 Technical characteristics
MECHANICAL FEATURES
Casing type Fitted on a door (160x220) or back-plate
Case material PC (Polycarbonate)
Protection degree
IP65 front panel /IP30 without gasket/
IP20 rear panel
Screen resolution 350x160 pixels – 8 lines of text
Weight 1085gr (controller without spare parts)
AC POWER
Rated voltage 120/208/230/240/277/400/480
Operating limits 110-480VAC (+-20%)
Frequency 50-60Hz +-10%
Drawn/Dissipated power <10W
Recommended fuses 1A gG
DC POWER
Rated battery voltage
DC Aux supply for IO modules
12-24VDC +/-20%
24VDC
Reverse polarity protection yes
Maximum drawn current 3A peak <10ms
Recommended fuses 1A gG
VOLTAGE SENSING
Ue max. Rated voltage 480Vac
Ui (according 60947-1) 600Vac
Measuring range limits 50-576Va
Frequency range limits 45-66Hz
Measurement type True RMS (TRMS)
Sample rate 9,6kHz
Measurement input impedance 6MΩ
Accuracy (V, U) 0,5%
Accuracy (f) 0,1%
CURRENT MEASUREMENT (WITH EXTERNAL CURRENT TRANSFORMERS (ONLY C65)
Ie rated current (secondary) Negative
Measuring range 6A max
Measurement type True RMS (TRMS)
Permanent thermal limit 5A max
Current Accuracy 1%
Power Accuracy 2%
Active Energy Accuracy 1%
DIGITAL INPUTS
Input type 1A or 5A
Input current 2,3mA at 24Vdc
Low input signal Let input floating for low signal
High input signal Link input with common to impose High level
Input signal delay <200ms

Table of Contents