ATySgM - 542933D - SOCOMEC
27EN
11.3. Network congurations
11.3.1. 230VAC network congurations (2P)
TEST
AUT
207 208 209 210 63 64 73 74
START
STOP
NOK
OK
POWER
Pn : 5VA
I max : 30A (35ms)
U = 176-288 Vac 45-65 Hz
!
U = 176-288 Vac 45-65 Hz
U U
5 A AC1
250 Vac
12 14 11
21 24 22
01 04 02
2 4 6
8
1
3
5 7
2 4 6 8
1 3 5 7
L1
L1
L1
L1
N
N
L1
L1
L2
L2
N
N
AUT
Priority
Load
SI SII
Type of network Terminal 1 Terminal 3 Terminal 5 Terminal 7
1BL - Single phase
N L1 N L1
L1 N L1 N
2BL - Two-phase L1 L2 L1 L2
11.3.2. Congurations réseau 230/400VAC (4P)
SI SII
1P
B
B
1P
3P
A
3P
A
N
L1 L2 L3
L1 L2 L3
N
N
L1 L2 L3
L1
L2 L3
N
N
L1
L1
N
N
L1
L1
N
TEST
/ PRIORITY
AUT
63 64
73 74
207 208 209 210 63 64 73 74
2A 30Vdc
1A 125Vac
0,5A 230Vac
resistive
max 60W or 250VA
2A 30Vdc
1A 125Vac
0,5A 230Vac
resistive
max 60W or 250VA
START
STOP
OK
NOK
2 4 6
8
1
3
5 7
2 4 6
8
1
3
5 7
2 4 6 8
1 3 5 7
2 4 6 8
1 3 5 7
AUT
5 A AC1
250 Vac
12 14 11
21 24 22
01 04 02
OKOK
OK
OK
Load
Type of network Position of the
first dip switch
Terminal
1
Terminal
3
Terminal
5
Terminal
7
1BL - Single
phase
1P - Position B
(dip switch down)
L1 / / N
N / / L1
4NBL - Three-
phase with
neutral
3P - Position A
(dip switch up)
L1 L2 L3 N
N L1 L2 L3
3NBL - Three-
phase without
neutral*
3P - Position A
(dip switch up)
L1 L2 L3 Neutral
transfo
Neutre
transfo
L3 L2 L1
In case of three-phase without neutral congurations you must rst congure the neutral position by wiring the
product for the rst time with a network 4NBL.