13.4.2. Three phase version
The LED signalling and operation is only active when the product supply is available.
To set the dip switches, it is necessary to open the Auto/Manual cover.
Commissioning must always result in having at least 1 LED source available on.
(Therefore, the voltage and frequency must be within the dened thresholds).
Any action on the potentiometers will change the settings, even when the cover is closed.
A
Dip switch settings
B
Source voltage supply
conguration
C
Timer settings
Type of network: A-B
A: 3P
B: 1P
Frequency: C-D
C: 50 Hz
D: 60 Hz
Stop in 0 position: E-F
E: No stop in O position
F: 2s stop in O position
Type of application: G-H
G: Network - Genset
H: Network - Network
Loss of priority source timer
FT
FT: 0-60 sec.
U/F
[HYST]
[HYST]
Return of priority sourcetimer
RT
RT: 0-30 min.
U/F
127/230 Vac
version
Un (P-P):
208-240 Vac
Un (P-N):
120-138 Vac
230/400 Vac
version
Un (P-P):
380-420 Vac
Un (P-N):
220-240 Vac
HYST: 20 %ΔU/F
ΔU: 5-20%
ΔF: 3-10%
D
LED info
Source availability LED
Source LED ON LED OFF LED blinking
Source 1 available
Source 1 not available
or out of range
- a timer is counting down
- test mode
Source 2 available
Source 2 not available
or out of range
- a timer is counting down
Fault reset
Fault and state of the product LED's
LED ON LED OFF LED blinking
Fault
Product OK or
S1-S2not available
Please wait
Auto mode Manual mode Manual retransfer
CDT and DTT timers are xed:
Genset cooling time : 4min and validation of secondary network / backup source stability = 5 sec.