EasyManua.ls Logo

socomec ATyS g M - Sealable Configuration Cover; Automatic Mode; Sealable Auto;Manual Cover; Possible Actions in Automatic Mode

socomec ATyS g M
54 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
ATySgM - 542933D - SOCOMEC
40 EN
13.7. Manual & Automatic Mode / Mains restoration conditions
Automatic mode returns to active 2 seconds after switching from manual to automatic mode.
Source
I
source
II
voltages and frequencies are checked to dene the changeover switch’s new stable status.
The same automatic mode recognition sequence must be executed following power-off and complete discharge of the
power reserves.
Mode settings
G
H
207 208
207 208
MODE 1
MODE 3
MODE 2
MODE 4
AUT
Priority
MODE
AUT
Priority
13.7.1. Mode 1: Automatic retransfer
Network - Genset applications
• Contact 207 / 208 open => automatic retransfer
NORMAL PRIORITY II TESTCommutation
de I vers II
Produit en
position I
Source
présente
Source
absente
Écoulement d’une
temporisation
207209
207209
TEST
TEST
5 sec.
4 min.
5 sec.
5 sec.
FT
5 sec.FT
Groupe
présent
Groupe
absent
Transfer
from I to II
Product in
position I
Source
available
Source
missing
Timer is
counting
down
Genset
available
Genset
missing
NORMAL PRIORITY II TEST

Table of Contents

Other manuals for socomec ATyS g M

Related product manuals