13.7. Manual & Automatic Mode / Mains restoration conditions
• Automatic mode returns to active 2 seconds after switching from manual to automatic mode.
• Source
I
source
II
voltages and frequencies are checked to dene the changeover switch’s new stable status.
• The same automatic mode recognition sequence must be executed following power-off and complete discharge of the
power reserves.
Mode settings
G
H
207 208
207 208
MODE 1
MODE 3
MODE 2
MODE 4
AUT
Priority
MODE
AUT
Priority
13.7.1. Mode 1: Automatic retransfer
Network - Genset applications
• Contact 207 / 208 open => automatic retransfer
NORMAL PRIORITY II TESTCommutation
de I vers II