ATYS input and output contacts

 
 
 
 
 
 
 
 
 
 
 
 


Denomination Terminal Description Characteristics Recommended
Cable Section
Signalisation
Outputs
13 



2

04 
14 
24 
63A

the ATYS is in Auto mode and motorisation is operational.
(No Fault powered and ready to changeover)
64A
Power supply
Input
301 



2

302 
Control Inputs 312 
Attn:



100m

2

313 
input forcing the product to remote control mode

314 
 
316 
 YS

CAUTION
Do not connect terminals 312 to 317 to any power supply. These order inputs are
powered through terminal 317 and external dry contacts ONLY.