ATYSp - 542001E - SOCOMEC
Dec.
Address
Hex.
Address
Words
count
Description Unit
21280 5320 1 Source 2: LAT Timer / 2CT state
1: Active
0: Not active
21281 5321 1 Source 2: 0RT Timer / 2OT state
1: Active
0: Not active
21282 5322 1 Source 2: FST Timer / 2ST state
1: Active
0: Not active
21283 5323 1 DBT Timer / 0DT state
1: Active
0: Not active
21284 5324 1 LoadShedding Timer (duration) / LST state
1: Active
0: Not active
21285 5325 1 TON (Test On Load Duration) Timer state
1: Active
0: Not active
21286 5326 1 T3T (Test on load end timer) Timer state
1: Active
0: Not active
21287 5327 1 TOF (Test Off Load Duration) Timer state
1: Active
0: Not active
21288 5328 1 STOLT (Time before Ord. Ext On Load) Timer / E1T state
1: Active
0: Not active
21289 5329 1 ETOLT (Time after Ord. Ext On Load) Timer / E3T state
1: Active
0: Not active
21290 532A 1 EOLTOT (Ord. Ext On Load Duration) Timer / E2T state
1: Active
0: Not active
21291 532B 1 STOFT (Time before Ord. Ext Off Load) Timer / E5T state
1: Active
0: Not active
21292 532C 1 ETOFT (Time after Ord. Ext Off Load) Timer / E7T state
1: Active
0: Not active
21293 532D 1 EOFTOF (Ord. Ext Off Load Duration) Timer / E6T state
1: Active
0: Not active
21294 532E 1 EET2: Secondary Source engine exerciser timeout / EET state
1: Active
0: Not active
21295 532F 1 EDT2: Secondary Source engine exerciser duration / EDT state
1: Active
0: Not active
AnnexeII-14.Optionmodulestate
Function 3 Codes
Dec.
Address
Hex.
Address
Words
count
Description Unit
21504 5400 2 Date & Time Current sec.