23816 5D08 1 In 5 - STO Board Input1 logical state
0: Not active
1: Active
23817 5D09 1 In 6 - STO Board Input2 logical state
0: Not active
1: Active
23818 5D0A 1 In 1 - External Display Board Input1 logical state
0: Not active
1: Active
23819 5D0B 1 In 2 - External Display Board Input2 logical state
0: Not active
1: Active
23820 5D0C 1 In 3 - External Display Board Input3 logical state
0: Not active
1: Active
23821 5D0D 1 In 4 - External Display Board Input4 logical state
0: Not active
1: Active
AnnexeII-26.Setuppulseand0/4-20mAoptionmodules
Function 3, 6 and 16 Codes
Dec.
Address
Hex.
Address
Words
count
Description Unit
23888 5D50 1 OUT 1 pulse output allocation
0: kWh+
1: kvarh +
2: kVAh
3: kWh -
4: kvarh -
5: Command
23889 5D51 1 OUT 1 pulse output value
0: 0,1 kWh/kvarh
1: 1 kWh/kvarh
2: 10 kWh/kvarh
3: 100 kWh/kvarh
4: 1000 kWh/kvarh
5: 10000 kWh/kvarh
23890 5D52 1 OUT 1 pulse output duration
0: 100ms
1: 200ms
2: 300ms
3: 400ms
4: 500ms
5: 600ms
6: 700ms
7: 800ms
8*: 900ms
23891 5D53 1 OUT 2 pulse output allocation
0: kWh+
1: kvarh +
2: kVAh
3: kWh -
4: kvarh -
5: Command