7.3.2.3. ATy
The ATySp can accept a total of 4 plug in I/O modules. (Attn: If using a communication module the total slots
available for extension I/O modules may be reduced to a maximum of 3 with MODBUS RTU and 2 with the Ethernet
module installed).
Outputs
Inputs
I
14
I
13
I
24
I
23
O
24
O
23
O
14
O
13
1
I
14
I
13
I
24
I
23
O
24
O
23
O
14
O
13
2
I
14
I
13
I
24
I
23
O
24
O
23
O
14
O
13
3
I
14
I
13
I
24
I
23
O
24
O
23
O
14
O
13
4
Out9
In13
Out8
In14
Out5
In9
Out4
In10
Out7
In11
Out6
In12
Out3
In7
Out2
In8
7.3.2.4. Terminal denomination, description and characteristics.
Denomination Terminal Description Characteristics Recommended
Cable Section
Output
Contacts
(Motorisation
Module)
04 Aux Contact Position 0 - Normally Open Contact
Dry Contacts
2A AC1 / 250V
2A/24VDC
1.5 – 2.5mm
2
13 Common for Aux Contacts positions I - 0 - II
14 Aux Contact position I: Normally Open Contact
24 Aux Contact position II: Normally Open Contact
63A Motorisation module available output. Closed
when the ATySp is in Auto mode and motorisation
is operational. (No Fault powered and ready to
changeover)
64A
ATS Output
Contact
63B Programmable output dry contacts. (By default
set as POP à ATS control module available output,
closed when the ATySp is in Auto mode and ATS
is operational. (No Fault, powered and ready for a
changeover sequence)
Dry Contacts 2A
AC1 / 250V
1.5 – 2.5mm
2
64B
GensetStart/
StopSignal
71 Signal to Start / Stop the Genset: Common for 72 & 74
Dry Contacts 2A
AC1 / 250V
1.5 – 2.5mm
2
72 Signal to Start / Stop the Genset: NC contact. (71/72)
74 Signal to Start / Stop the Genset: NO contact. (71/74)
AdditionalAux
Contact
Included with
2000A to
3200A
81 Common for Aux Contacts positions I
Dry Contacts 2A
AC1 / 250V
1.5 – 2.5mm
2
82 Aux Contact position I: Normally Closed Contact
84 Aux Contact position I: Normally Open Contact
91 Common for Aux Contacts positions II
92 Aux Contact position II: Normally Closed Contact
94 Aux Contact position II: Normally Open Contact
ATS Power
supply Input I
101 - L/N Power supply I – L/N
208 - 277VAC ± 20%:
50/60Hz
1.5 – 2.5mm
2
102 - N/L Power supply I – N/L
ATSVoltage
SensingInput*
SwitchI
103 - 7/8 Phase or neutral connected on power contact 7 or 8
of Switch I
575 VAC
(ph-ph) max
332Vac
(ph-n) max
1.5 – 2.5mm
2
104 - 5/6 Phase connected on power contact 5 or 6 of Switch
I
105 - 3/4 Phase connected on power contact 3 or 4 of Switch
I
106 - 1/2 Phase or neutral connected on power contact 1 or 2
of Switch I
ATS Power
supply Input II
201 - L/N Power supply II – L/N
208 - 277VAC ± 20%:
50/60Hz
1.5 – 2.5mm
2
202 - N/L Power supply II – N/L

Table of Contents