99
EN
ATYSp - 542001E - SOCOMEC
AnnexeI-11.4.Operationofloadsheddingbeforetransfer
If output LSC is selected, (load shedding before transfer request), the associated time delay LST (maximum duration
of the load shedding) must be programmed in the Timers Menu.
Scenario1withLSIactive
Source 1 Source 1
Source 2
1FT
2AT
1RT
GE start order
2CT
LSC output
LST delay (> 2AT)
Positions
Load
Source 1 Source 1
Source 2
1FT
2AT
1RT
GE start order
2CT
LSC output
Valid from the leading edge
LSI input
(Bypass Tempo LST)
LST delay (> 2AT)
Positions
Load
0DT
0
I
Sources
I II
ODT
0
0DT
Sources
ODT
II
0
II
Gen set start delay
Gen set start delay
Shedding
Load shed
Load shed
Shedding
Scenario2:LSIInputnotactivated
Source 1 Source 1
Source 2
1FT
2AT
1RT
GE start order
2CT
LSC output
LST delay (> 2AT)
Positions
Load
Source 1 Source 1
Source 2
1FT
2AT
1RT
GE start order
2CT
LSC output
Valid from the leading edge
LSI input
(Bypass Tempo LST)
LST delay (> 2AT)
Positions
Load
0DT
0
I
Sources
I II
ODT
0
0DT
Sources
ODT
II
0
II
Gen set start delay
Gen set start delay
Shedding
Load shed
Load shed
Shedding
AnnexeI-12.Communicationmenu–keypadnavigation
7
COMM
Definition AdjustmentRange
DHCP NO
Dynamic Host Conguration Protocol YES / NO
IP 1-2 192.168.
IP Address Line 1 -
IP 3-4 .002.001
IP Address Line 2 -
GAT1-2 000.000.
Gate Line 1 -
GAT3-4 .000.000
Gate Line 2 -
MSK1-2 255.255.
Mask Line 1 -
MSK3-4 .255.000
Mask Line 2 -
ADDRESS 005
ATySp Device network address: 1 to 255
BDRATE 9600
Baud rate: 9600, 19200
38400
STOP BIT 1
Stop Bit Setting 1, 2