EasyManua.ls Logo

socomec DIRIS A40 - TABLE E220 Hex: Ethernet configuration

socomec DIRIS A40
27 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
MAN 06 033774 technical_guide_ DIRIS_A40_A41_C.doc40/Z41 - B 21/27
4.3 - Modification of DIRIS configuration with “writing” function.
Configuration of CT primary (address Hex. 202) : TC = 1500 = 05DC en hexadecimal
Master request:
Slave
Function
Address
Address
Value
Value
CRC16
High-order
Low-order
High-order
Low-order
07
06
02
02
05
DC
2B1D
1500 in decimal
DIRIS reply:
Identical to master request
After having modified the parameters of the DIRIS, and to record them, it is necessary to send
the backup order:
Slave
Function
Address
Address
Value
Value
CRC16
High-order
Low-order
High-order
Low-order
07
06
06
00
00
00
8924
DIRIS reply:
The DIRIS does not answer this order.
Configuration of network type (address Hex. 200) , Type = 3 NBL = 3 in hexadecimal
Master request :
Slave
Function
Address
Address
Value
Value
CRC16
High-order
Low-order
High-order
Low-order
07
06
02
00
00
03
C815
3 NBL
DIRIS reply:
The DIRIS does not answer this order.
After having modified the parameters of the DIRIS, and to record them, it is necessary to send
the saving order:
Slave
Function
Address
Address
Value
Value
CRC16
High-order
Low-order
High-order
Low-order
07
06
06
00
00
00
8924
DIRIS response:
The DIRIS does not answer this order.

Other manuals for socomec DIRIS A40