MAN 06 033774 technical_guide_ DIRIS_A40_A41_C.doc40/Z41 - B 24/27
Address Hex
Decimal value
(W/10)
Date and time
Value without
CT and VT ratio
(W)
Value multiply
by CT and VT
ration (W)
TC = 10000/5
304D
5828
31/07/06 15 :30 :00
582.8
1165600
304E
4796
31/07/06 15 :40 :00
476.6
953200
304F
3597
31/07/06 15 :50 :00
359.7
719400
3050
5467
31/07/06 16 :00 :00
546.7
1093400
3051
5882
31/07/06 16 :10 :00
588.2
1176400
NB :
When DIRIS is switch off (MHT), this information is coded in the following way
First word star always with $Exxx
Adress + 0
$Emdd
1 word
m : month 1 to 12
dd : day 1 to 31
Adress + 1
$hhnn
1 word
hh : hours 0 to 23
nn : minutes 0 to 60
Adress + 2
$ssyy
1 word
ss : secondes 0 to 59
yy : year 0 à 255
When DIRIS is switch on (MST), this information is coded in the following way
First word star always with $Fxxx
Adress + 0
$Fmdd
1 word
m : month 1 to 12
dd : day 1 to 31
Adress + 1
$hhnn
1 word
hh : hours 0 to 23
nn : minutes 0 to 60
Adress + 2
$ssyy
1 word
ss : secondes 0 to 59
yy : year 0 à 255
The recorded average power, between DIRIS starting and the following interval of time, is framed by two MST. See
below :