54
DIRIS A40/A41 - Ref.: 535 747 A
GB
DIRIS A40 /A41
CARACTÉRISTIQUES TECHNIQUES
TECHNICAL CHARACTERISTICS - TECHNISCHE DATEN -
CARATTERISTICHE TECNICHE - TECHNISCHE EIGENSCHAPPEN -
CARACTERÍSTICAS TÉCNICAS - CARACTERÍSTICAS TÉCNICAS
CONFORMITE IEC 61557-12 Edition 1 (08/2007)
CARACTÉRISTIQUES DU PMD
Type of specification Examples of possible specification values Other additional
specifications
Supply quality evaluation
function (optional)
--
PMD classification SD -
Setpoint K55 -
Humidity + Altitude - -
Operating performance
class for active power or
active energy (if function
available)
0,5 -
CARACTÉRISTIQUES DES FONCTIONS
Symbols for functions Measurement range Operating performance class,
according to CEI 61557-12
Other additional
specifications
KI 1000 100 10 1
P - 0,5 - - 2 from -90° to +90°
Qa, Qv - 1 - - 2 -
Sa, Sv
-1--- -
Ea 0 to 99999999 kW/h
0,5 - - -
from 0,02 to 1,2 In with PF =
0,5L or 0,8C
Era, Erv 0 to 99999999 kVar/h
1---
from 0,1 to 1,2 In with sin
J =
0,5 L or C
Eapa, Eapv 0 to 99999999 kW/h 0,5 - - - -
f 45 to 65 Hz 0,02 - - - -
I 0,1 to 1,2 A for TC 1A
0,5 to 6 A for TC 5A
0,2
---
from 10 to 110% / In ( In = 1
or 5A according to CT )
In, Inc 0,1 to 1,2 A for TC 1A
0,5 to 6 A for TC 5A
0,2
---
10 to 110% / In ( In = 1 or 5A
according to CT )
U
50 to 600 V (phase/phase)
0,2 - - -
-
PFa ,PFv - 0,5 - - - pour 0,5< PF<1
Pst, Plt - - - - -
Udip
50 to 600 V (phase/phase)
0,2 ou
0,5
--- -
Uswl
50 to 600 V (phase/phase)
0,2 ou
0,5
--- -
Utr - - - - - -
Uint
50 to 600 V (phase/phase)
0,5 - - - -
Unba - - - - - -
Unb - - - - - -
Uh
50 to 600 V (phase/phase)
1--- -
THDu
50 to 600 V (phase/phase)
1--- -
THD-Ru
- ---- -
Ih 0,1 to 1,2 A for TC 1A
0,5 to 6 A for TC 5A
1--- -
THDi 0,1 to 1,2 A for TC 1A
0,5 to 6 A for TC 5A
1--- -
THD_Ri
- ---- -
Msv - - - - - -
Shop for Power Metering products online at:
1.888.610.7664
www.PowerMeterStore.com