45EN
DIRIS DIGIWARE DC - 545830B - SOCOMEC
11. ALARMS
The threshold alarms are only available in DIRIS Digiware U-31dc, U32dc, I-35dc and IO-20.
The alarms on digital inputs with change of output status are only available in DIRIS DigiwareIO-10.
11.1. Alarms upon events
Alarms can be generated when a threshold is exceeded for the electrical measurements, consumption, variations in
level or change in input status. Also, combinations can be made on the alarms created.
Up to 25 alarms detected are saved and timestamped; an alarm can have 3 distinct statuses: Alarm active, Alarm
completed, Alarm completed and acknowledged. Alarms can be acknowledged either automatically or by user
action, as required.
Up to 8 alarms for an electrical measurement can be congured per equipment and 4 for changes in status of a
digital input. The digital inputs are available only on DIRIS Digiware IO-10 modules.
The alarms are congured via the Easy Cong software.
11.1.1. Electrical parameters
The alarms available will be based on electrical parameters measured in the products.
• Alarm upon variation in the instantaneous or average value of an electrical value: Current, voltage, power or an
analogue value on the DIRIS Digiware IO-20 module.
• Selection of the hysteresis and high/low threshold.
• Setting a time delay at the start and end of the alarm.
Example of conguring an alarm on the current via Easy Cong:
11.1.2. Consumption
• Alarm on the energies: partial Ea+, Ea-
• Selection of a high threshold (excessive consumption)