46 EN
DIRIS DIGIWARE DC - 545830B - SOCOMEC
11.1.3. Combination of alarms
• Up to 4 boolean combinations (OR, AND) on the dened alarms (electrical values, energy, inputs, etc.)
Example of conguring an alarm on a digital input via Easy Cong:
11.2. System alarm
If a saturation of voltage input is detected, an alarm will be automatically generated.
11.3. Setting up alarms
The system alarms are automatically detected and alarms upon events are congured with the Easy Cong
software.
There are several ways of identifying the presence of an alarm:
11.3.1. ALARM LED on front
• Blinking: Alarm system (priority on alarm upon events)
• Fixed: Event alarm
11.3.2. Activation of an output
• On the DIRIS Digiware IO-10 an output may be enabled when an alarm is detected
11.3.3. Activation of an input
• If an input is present, the alarm can be acknowledged from this input. Acknowledgement of an alarm can only be
taken into account if the alarm is complete
11.3.4. RS485 Modbus
• Information on the alarms with timestamping available via the RS485 communication bus
• Alarm acknowledgement
11.3.5. Display and WEBVIEW
• Information on the alarms with timestamping
• Alarm acknowledgement