49EN
DIRIS DIGIWARE DC - 545830B - SOCOMEC
Connection Removable screw terminal block, 3 positions, stranded or solid
0.14-1.5mm² cable
USB
Protocol
Modbus RTU on USB
Function
Configuration of DIRIS Digiware U and I modules
Location
On each DIRIS Digiware U and I measurement module
Connection
Type B micro USB connector
12.1.5. Environmental characteristics
Ambient operating temperature
-10-+70°C (IEC 60068-2-1/IEC 60068-2-2)
Storage temperature
-25-+70°C (IEC 60068-2-1/IEC 60068-2-2)
Operating humidity
55°C / 97%RH (IEC 60068-2-30)
Operating altitude
< 2000 m
Vibration 0.35mm, 25Hz, 20 min/axe (IEC 61557-12)
Impact resistance Front panel: 1J - casing: 1J (IEC 61010-1 Ed 3.0)
PEP ecopassport - ISO 14025 DIRIS Digiware DC : SOCO-00008-V01.01-EN,
DIRIS Digiware IO : SOCO-00001-V01.01-EN
12.1.6. Electromagnetic characteristics
Immunity to electrostatic discharges on contact IEC 61000-4-2 LEVEL III Criterion A
Immunity to electrostatic fields in the air IEC 61000-4-2 LEVEL III Criterion A
Immunity to radiated electromagnetic fields 80MHz to 1GHz IEC 61000-4-3 LEVEL III Criterion A
Immunity to radiated electromagnetic fields 1.4GHz to 2.7GHz IEC 61000-4-3 LEVEL III Criterion A
Immunity to electrical fast transients/bursts IEC 61000-4-4 LEVEL IV Criterion A
Surge immunity in common mode IEC 61000-4-5 LEVEL II Criterion B
Immunity to conducted disturbances IEC 61000-4-6 LEVEL II Criterion A
Immunity to power frequency magnetic elds IEC 61000-4-8 400A/m Criterion A
Radiated emissions CISPR11 Group 1 - CLASS B
Electromagnetic environment Basic & industrial
12.1.7. Safety
Safety
Low Voltage Directive conformity:
2014/35/EU of 26 February 2014 (IEC EN61010-1 & IEC EN61010-2-030)
Electromagnetic Compatibility Directive conformity:
2014/30/EU of 26 February 2014
Insulation Degree of pollution 2
Measurement category: CAT III
UL UL61010-1 & UL61010-2-030
UL installation:
DIRIS Digiware DC and current sensors have to be enclosed inside
an NRTL certied electrical/re enclosure, Listed Industrial Control
Equipment, or similar equipment.
The DC current sensors have to be compatible with the specications
provided in this manual and UL Listed with internal burden
components.