6.4. Connecting the current sensors
6.4.1. Connection concept
DIRIS Digiware
I-3xdc
RJ12-Terminal
cables
3x
DC Current
sensors
- Use only DC current sensors complying with the characteristics
(see “4.2. Current sensors”, page 16).
- Do not use AC current sensor for DIRIS Digiware type TE, TR and TF.
- For connecting the current sensors, use SOCOMEC cables or equivalent only, RJ12-Terminal
straight cables, twisted pair, unshielded, 600V, -10°C / +70°C.
- Ensure that the connection of the cable to the sensor is correctly maintained.
- It is recommended that all the current sensors are installed in the same direction.
- Always connect input I01 rst.