DIRIS DIGIWARE DC - 545830B - SOCOMEC
8. STATUS AND AUTO-ADDRESSING LEDS
8.1. Status LEDs
These LEDs can be used to nd out the status of the product at any time.
The addressing button is used to automatically assign a Modbus address from the gateway.
Power supply
Alarm
Communication
Metrology
Addressing button
LED state Fixed Blinking Pulse
ON
In operation 10 seconds - on request via a
Modbus control to identify the
device (remote screen, etc.)
1 second to start-up
ALARM
An alarm (logical/analogue, etc.)
is active (doesn’t take priority if
there is a system alarm at the
same time)
An alarm system indicating the
saturation of a voltage input on
the voltage measurement module
U-3xdc is enabled.
(possible presence of too high a
common mode voltage)
1 second to start-up
COM
Addressing problem. Address OK 1 second to start-up and when a
frame received is processed
- - Corresponds to the metrological
pulse weight (pulse weight:
0.1Wh)
8.2. Auto-addressing
With auto-addressing mode you can have the system automatically assign addresses to products connected to the
DIRIS G gateways or DIRIS Digiware D remote displays. This mode is only compatible with DIRIS B-30 and DIRIS
Digiware PMDs. The addresses will be allocated manually on the other PMD (DIRIS A) and meters (COUNTIS).
Two modes are available:
Mode 1 - Auto-detection and automatic addressing
Mode 2 - Auto-detection and address selection
Mode 1 is without external equipment (see description below).
Mode 2 is carried out from a PC equipped with EasyCong.